174
Section 2 Installation
Temporary Wiring
Temporary wiring is done to provide
electrical power only during construction,
remodeling, demolition, repair, or large-scale
maintenance of a building. This wiring must
be removed when the work is completed.
Article 590 of the NEC covers this subject.
Although temporary wiring safety
requirements may be less exacting than perma-
nent wiring, most of the same rules apply.
However, there are several important differ-
ences. Temporary wiring can be used on a
construction site during the entire term of
construction, regardless of the type of
construction, Figure 10-17. In addition, tempo-
rary power can be brought in for emergency
situations, testing, and experimentation.
The key factors for installation of all tempo-
rary wiring are:
All temporary wiring, devices, and equip-
ment should be located in a safe place and
should be as neat as possible. Temporary
wiring should be kept overhead as much as
possible.
All 15-, 20-, and 30-amp receptacles require
GFCI protection.
Protect temporary wiring from physical
damage.
Use portable ground-fault circuit inter-
rupter boxes. See Figure 10-18.
Grounding must be in compliance with
Article 250 of the NEC.
All lamps should have protective covers or
caging. They should be mounted at heights
of 7′ or higher.
All circuits must originate from approved
panels or power outlets and must have
overcurrent protection.
Receptacle circuits and lighting circuits
must be separated.
Weatherproof devices and housings should
be used wherever there is dampness or expo-
sure to weather.
Locking type plugs and connectors should
be used on power ends.
Temporary wiring should be inspected
frequently for damage.
Disconnects
Meters
Figure 10-17. These are typical temporary service installations installed at construction sites.
temporary wiring: A method of providing electrical
power only during construction, remodeling, demoli-
tion, repair, or large-scale maintenance of a building.
Previous Page Next Page