Chapter  6  Conductors  93  Copyright  Goodheart-Willcox  Co.,  Inc.  6.3.1  Ampacity  Correction  Factors  The  allowable  ampacities  listed  in  Tables  310.15(B)(16)  through  310.15(B)(19)  are  only  applicable  for  a  specific  number  of  conduc-  fi  tors  and  a  specifi  ambient  temperature:  fic  •  one  conductor  in  Tables  310.15(B)(17)  and  310.15(B)(19)  •  three  conductors  or  less  in  Tables  310.15(B)(16)  and  310.15(B)(18)  •  86°F  (30°C)  ambient  temperature  in  Tables  310.15(B)(16)  and  310.15(B)(17)  •  104°F  (40°C)  ambient  temperature  in  Tables  310.15(B)(18)  and  310.15(B)(19).  When  there  are  more  than  three  conduc-  tors  in  a  raceway  or  the  ambient  temperature  differs  from  the  table  values,  corrections  must  be  made.  Table  310.15(B)(2)(a)  contains  temperature  correction  factors,  Figure  6-8.  Ambient  tem-  peratures  are  listed  on  both  sides  of  the  fac-  tors:  Celsius  on  the  left  and  Fahrenheit  on  the  right.  The  correction  factor  is  multiplied  by  the  allowable  ampacity  from  the  table  to  determine  the  allowable  ampacity  for  a  different  ambient  temperature.  The  ampacities  of  different  conductor  types  vary  differently  with  temperature  change.  Therefore,  each  type  of  conductor  has  unique  temperature  corrections.  As  the  ambient  tem-  perature  increases,  the  ampacity  of  the  conduc-  tor  is  reduced.  SAMPLE  PROBLEM  6-3  Problem:  Three  aluminum  type  THWN  con  nd  uctors  have  been  specified  to  carry  65  amps  throug  gh  rigid  fi  non-metallic  conduit.  What  size  conductor  rs  are  needed?  Solution:  Looking  in  the  aluminum  THWN  W  column  of  Table  310.15(B)(16),  65  amps  is  found  in  the  e  4  AWG  row.  Therefore,  the  4  AWG  aluminum  THWN  W  conductors  are  the  smallest  conductors  allowed.  Table  310.15(B)(16)  (formerly  Table  310.16)  Allo  ow  able  Ampacities  of  Insulated  Conductors  Rated  Up  to  and  Includi  d  in  g  2000  Volts,  60°C  °  Through  90°C  °  (140°F  °  Through  1  19  4°F),  °  Not  More  than  Three  Current-Carrying  Conductors  in  Race  ew  ay,  Cable,  or  Earth  (Directly  Buried),  Based  on  Ambient  Temperature  em  of  30°C  °  (86°F)*°  Temperature  ur  Rating  of  Conductor  [See  Table  310.104(A).]  60°C  75°C  90°C  60°C  75°C  °  90°C  (140°F)  (167°F)  (194°F)  (140°F)  (167°F)  (194°F)°  Types  TBS,  SA,  SIS,  F  FE  P,  FEPB,  MI,  RHH,  Types  TBS,  SA,  SIS,  S  RHW-2,  THHN,  THHN,  THHW  W,  Types  RHW,  THHW,  THW-2,  Types  RHW,  THW-2,  THWN  N-2,  THHW,  THW,  THWN-2,  USE-2,  XHH,  THHW,  THW,  RHH,  RHW-2,  U  USE  -2,  Types  TW,  THWN,  XHHW,  XHHW,  XHHW-2,  Types  TW,  THWN,  XHHW,  XHH,  XHHW,  HW  THWN,  UF  USE,  ZW  ZW-2  UF  USE  XHHW-2,  ZW  W-  2  COPPER  PE  ALUMINUM  OR  COPPER-CLAD  ALUMIN  NU  M  A  LUMINUM  18  —  —  14  —  —  —  —  16  —  —  18  —  —  —  —  —  14**  15  20  25  —  —  —  —  —  12**  20  25  30  15  20  2  25  12**  10**  30  35  40  25  30  35  10**  8  40  50  55  35  40  45  8  6  55  65  75  40  50  55  6  95  55  65  75  4  65  4  70  85  5  3  85  100  0  0  115  65  75  85  3  2  95  115  1  130  75  90  100  2  Size  AWG  or  kcmil  Size  AWG  or  k  il  95  55  70  85  —  —  —  20  30  40  50  50  50  4  Copyright  ©  2016  NFPA  
